Methyl mercaptan

NO.71H
CH3SH
Performance
Measuring Range
20 to 50 ppm 50 to 1000 ppm 1000 to 2700 ppm
Number of Pump Strokes
2 1 1/2
Correction Factor
0.4 1 2.7
Sampling Time 1 minute per pump stroke
Detecting Limit 2 ppm (n=2)
Colour Change White → Yellow
Reaction Principle 2CH3SH + PdSO4 → (CH3S)2Pd + H2SO4
Coefficient of Variation 10% (for 50 to 200 ppm), 5% (for 200 to 1000 ppm)
Shelf Life 3 Years
Corrections for temperature & humidity Unnecessary
Store the tubes at cool and dark place.
Possible coexisting substances and their interferences (NOTE)
Substance Concentration Interference Change colour by itself to
Carbon monoxide   No No
Nitrogen dioxide   No No
Hydrogen sulphide 1000 ppm + No
Ethylene   No No
Mercaptans   + Yellow
Other substance measurable with this detector tube
Substance Correction Factor No. of pump strokes Measuring Range
Ethyl mercaptan by scale 1 100 to 3800 ppm
Calibration gas generation Static gas dilution method
TLV-TWA TLV-STEL Explosive range
0.5 ppm - 3.9 to 21.8%


Return to previous viewGo to top of page