Ethyl mercaptan |
NO.72L |
Measuring Range |
|
|||
Number of Pump Strokes |
|
|||
Correction Factor |
|
|||
Sampling Time | 1.5 minutes per pump stroke | |||
Detecting Limit | 0.15 ppm (n=2) | |||
Colour Change | Yellow → Red | |||
Reaction Principle | C2H5SH + HgCl2 →ClH5S HgCl + HCl |
|||
Coefficient of Variation | 10% (for 0.5 to 5 ppm), 5% (for 5 to 30 ppm) | |||
Shelf Life | 2 Years | |||
Corrections for temperature & humidity | Temperature correction is necessary | |||
Store the tubes at cool and dark place. |
Substance | Concentration | Interference | Change colour by itself to |
Hydrogen sulphide | + | Red | |
Mercaptans | + | Red | |
Acetylene | + | No | |
Carbon monoxide | + | No | |
Ethylene | + | No |
Calibration gas generation | Permeation tube method |
TLV-TWA | TLV-STEL | Explosive range |
10 ppm | - | 2.8 to 18.2% |