F-Guard IR3-HD CO2L
Triple IR Flame Detector, the FlameSpec IR3 will detect fires and explosions extremely quickly, thereby allowing mitigation steps to be initiated more rapidly to limit event escalation.
List of Benefits
- Highest immunity to false alarms
- Hydrocarbon flame detection. Three wavelengths, in the infrared spectral range of 4.0 to 5.0 μm, with clear separation.
- Each sensor has the same field of view to further improve false alarm immunity.
- HD, or composite, video output with automatic HD video recording of events.
- Ultra-fast detection within 40 milliseconds for fireballs or explosions.
- Detects up to 262 ft. (80m) for a 1 ft2 (0.1m2) n-heptane fire.
- 5 selectable sensitivity levels.
- Data/Event logger: Alarms, faults & videos are logged to non-volatile memory.
- Universal outputs, 3 and 4 wire, 4-20 mA sink / source, Fire, Auxiliary and Fault Relays. RS485 port using Modbus RTU.
- Built-in-Test (BIT) – Automatic and manual self-test of window cleanliness and overall detector operation.
- HART® 7, as standard - Easy configuration and diagnostic capability, including dirty optics warning for preventive maintenance needs.
- Window heater to avoid condensation and icing.
- Stainless steel tilt mount with horizontal and vertical adjustment.
- SIL 2 compliant - suitable for use as part of a SIL 2 compliant safety system.
The FlameSpec-IR3-HD CO2L flame detector has been optimised to provide fast, robust detection for a wide range of heavy hydrocarbon fires, where combustion exhaust gases may be present.
The detector also provides a high-definition (HD) colour video output of the monitored area with clear imaging of events and personnel up to 100 ft. (30m) allowing responders to know the exact situation before entering the hazardous area. Video and data of events are stored saved quickly to non-volatile memory for post incident investigation.
The recordings start one minute before detection and continue for up to four minutes.
Typical applications include:
- Aircraft hangars
- Hardened aircraft shelters
- Helipads (Onshore, Offshore,Hospitals)
- Areas with high vehicle activity:
- Waste recycling facilities
- Road / Rail tanker loading racks
Specification | Detail Description |
---|---|
FIRE DETECTION | |
Detection time and distance | 40ms for fast fire burst or explosion, 1.5s for 1 ft² (0.1m²) pan fire at 0–100 ft. (0–30m), 4.1s for 1 ft² (0.1m²) pan fire at 100–230 ft. (30–70m) |
Sensitivity range | 5 sensitivity ranges (Extreme, High, Medium, Low, Very Low) |
Field of view (IR detection) | 90° Horizontal, 75° Vertical |
Time Delay | 0-30 seconds |
Built in Test | Automatic and Manual |
VIDEO FUNCTIONALITY | |
HD Video | Color HD, as standard. Near IR filtered option (X2 available on request) |
Video recording of alarm events | 1-minute pre-event and 3 minutes post-event |
System integration protocol | ONVIF (Open Network Video Interface Forum) Profile S |
ELECTRICAL SPECIFICATIONS | |
Operating Voltage | 24 VDC nominal (18-32 VDC) |
Current Consumption | Standby = 180mA, Maximum = 300mA all systems in operation (including window heater) |
Electrical Entries | 2x conduit entries 3/4” NPT(F) or M25x1.5 |
Wiring | 12-20AWG (2.5–0.35mm²) |
OUTPUTS | |
Relays | SPST volt-free contacts rated 2A at 30 VDC, 3 relays = Alarm & Auxiliary – normally open; Fault– normally closed |
0-20mA (stepped) current output | 3 wire and 4 wire (isolated) configurations (sink and source), HART® rev 7.0 |
Indication | Tri-color LED |
Modbus | RTU compatible on RS-485 |
Digital (for video) | IP network IEEE 802.3 100Base-T |
Composite video | NTSC or PAL |
MECHANICAL SPECIFICATIONS | |
Size | 140 x 90 x 90mm |
Weight | Detector (Stainless Steel 316) |
ENVIRONMENTAL SPECIFICATIONS | |
Temperature Range | Operating = -67°F to +167°F (-55°C to +75°C), Storage = -67°F to +185°F (-55°C to +85°C) |
Humidity | Up to 99% (RH), non-condensing |
Ingress Protection | IP66 & 68; NEMA 4X & 6P |
APPROVALS* | |
ATEX | ATEX II 2 G D, Ex db IIC T5 Gb or Ex db eb IIC T5 Gb and Ex tb IIIC T95°C Db -55°C |
IECEx & PESO | Ex db IIC T5 Gb -50°C≤Ta≤75°C, Ex db IIC T4 Gb -50°C≤Ta≤85°C |
FMus & FMc | Class I, Div. 1, Groups B, C & D; T4, Class I, Zone 1, AEx/Ex db IIC T4 Gb, T4 -50°C≤Ta≤85°C, T5 -50°C≤Ta≤75°C |
EAC CU TR | 1Ex d IIC T5 Gb or 1Ex de IIC T5 Gb and Ex tb IIIC T95°C Db -55°C≤Ta≤75°C, 1Ex d IIC T4 Gb or 1Ex de IIC T4 Gb and Ex tb IIIC T105°C Db -55°C≤Ta≤85°C |
Performance | ANSI FM 3260, EN 54-10 |
Functional safety (pending) | SIL2, per IEC 61508 |
ACCESSORIES | Stainless steel weather cover, model FLS-WCO-S02, Flame simulator, model FLS-FSIM-IR3-KIT, 2” & 3” pole mount adapter, model FLS-PMA-S23, Airshield for areas with high airborne contamination, model FLS-ASD-S02 |
WARRANTY | 5 years |