F-Guard IR3 CO2L

Triple IR Flame Detector. The FlameSpec IR3 will detect fires and explosions extremely quickly, thereby allowing mitigation steps to be initiated more rapidly to limit event escalation.

List of Benefits

  • Highest levels of false alarm immunity.
  • Detects up to 262 ft. (80m) for a 1 ft2 (0.1m2) n-heptane pan fire.
  • Hydrocarbon flame detection. Three wavelengths, in the infrared
  • spectral range of 4.0 to 5.0 μm, with clear separation.
  • Each sensor has the same field of view to further improve false alarm immunity.
  • Ultra-fast detection mode – detection within 40 milliseconds for fireballs or explosions.
  • Fast flame detection, <1.5 s for standard fire up to 30 m. Option for <0.5s, in compliance with NFPA 33, available.
  • 5 selectable sensitivity levels
  • Universal outputs, 3 and 4 wire, 4-20 mA sink / source, Fire, Auxiliary and Fault Relays. RS485 port using Modbus RTU.
  • Event logger – alarms & faults are logged to non-volatile memory.
  • Built-in-Test (BIT) – Automatic and manual self-test of window cleanliness and overall detector operation.
  • Dirty optics warning for preventive maintenance needs.
  • HART® 7, as standard. Enhanced configuration & maintenance.
  • Window heater to avoid condensation and icing.
  • Stainless steel tilt mount provides horizontal and vertical adjustment.
  • SIL 2 compliant - suitable for use as part of a SIL 2 compliant safety system.

 
The FlameSpec-IR3 CO2L flame detector has been optimized to provide a fast, robust detection of a wide range of heavy hydrocarbon fires, where combustion exhaust gases may be present, and standard IR3 detectors might false alarm. Typical applications include:
  • Aircraft hangars
  • Hardened aircraft shelters
  • Helipads (Onshore, Offshore,Hospitals)
  • Areas with high vehicle activity:
    • Waste recycling facilities
    • Road / Rail tanker loading racks
SpecificationDetail Description
FIRE DETECTION
Detection time and distance40ms for fast fire burst or explosion, 1.5s for 1 ft² (0.1m²) pan fire at 0–100 ft. (0–30m), 4.1s for 1 ft² (0.1m²) pan fire at 100–230 ft. (30–70m)
Sensitivity range 5 sensitivity ranges (Extreme, High, Medium, Low, Very Low)
Field of view (IR detection)90° Horizontal, 75° Vertical
Time Delay0-30 seconds
Built in TestAutomatic and Manual
ELECTRICAL SPECIFICATIONS
Operating Voltage24 VDC nominal (18-32 VDC)
Current Consumption Standby = 180mA, Maximum = 300mA all systems in operation (including window heater)
Electrical Entries2x conduit entries 3/4” NPT(F) or M25x1.5
Wiring12-20AWG (2.5–0.35mm²)
OUTPUTS
RelaysSPST volt-free contacts rated 2A at 30 VDC, 3 relays = Alarm & Auxiliary – normally open; Fault– normally closed
0-20mA (stepped) current output 3 wire and 4 wire (isolated) configurations (sink and source), HART® rev 7.0
IndicationTri-color LED
ModbusRTU compatible on RS-485
Digital (for video)IP network IEEE 802.3 100Base-T
Composite videoNTSC or PAL
MECHANICAL SPECIFICATIONS
Size140 x 90 x 90mm
WeightDetector (Stainless Steel 316)
ENVIRONMENTAL SPECIFICATIONS
Temperature Range Operating = -67°F to +167°F (-55°C to +75°C), Storage = -67°F to +185°F (-55°C to +85°C)
Humidity Up to 99% (RH), non-condensing
Ingress Protection IP66 & 68; NEMA 4X & 6P
APPROVALS*
ATEX ATEX II 2 G D, Ex db IIC T5 Gb or Ex db eb IIC T5 Gb and Ex tb IIIC T95°C Db -55°C
IECEx & PESO Ex db IIC T5 Gb -50°C≤Ta≤75°C, Ex db IIC T4 Gb -50°C≤Ta≤85°C
FMus & FMc Class I, Div. 1, Groups B, C & D; T4, Class I, Zone 1, AEx/Ex db IIC T4 Gb, T4 -50°C≤Ta≤85°C, T5 -50°C≤Ta≤75°C
EAC CU TR 1Ex d IIC T5 Gb or 1Ex de IIC T5 Gb and Ex tb IIIC T95°C Db -55°C≤Ta≤75°C, 1Ex d IIC T4 Gb or 1Ex de IIC T4 Gb and Ex tb IIIC T105°C Db -55°C≤Ta≤85°C
PerformanceANSI FM 3260, EN 54-10
Functional safety (pending) SIL2, per IEC 61508
ACCESSORIES Stainless steel weather cover, model FLS-WCO-S02, Flame simulator, model FLS-FSIM-IR3-KIT, 2” & 3” pole mount adapter, model FLS-PMA-S23, Airshield for areas with high airborne contamination, model FLS-ASD-S02
WARRANTY 5 years
 