F-Guard IR3 H2-HD
The Gastech F-Guard-lR3-H2-HD flame detector provides ultra-fast response, high performance and reliable detection of hydrogen (H2) fires
List of Benefits
- High immunity to false alarm
- Ultra-fast detection mode detection within 40 milliseconds for Hydrogen fireballs or explosions
- Hydrogen flame detection
- High sensitivity -up to 100 ft.(30m)
- HD video output with Automatic HD video recording of fire events
- Data/Event logger -alarms, faults and other relevant events are logged to non-volatile memory
- Ethernet communication - in addition to the standard methods, such as 4-20mA and Modbus
- Built-in-Test (BIT) -Automatic and manual internal self-test of window cleanliness and the overall operation of the detector
- Window heater to avoid condensation and icing
- Tilt mounting bracket can be connected either above or below the detector.
The detector addresses slow growing fires as well as fast eruptions of fire using improved IR3 technology. The detector operates in all weather and light conditions.
In addition, the detector provides high-definition (HD) video output of the monitored area with clear imaging of a fire event and of personnel at distances up to 100 ft. (30m). This allows the rescue team to be aware of the exact situation before entering the hazardous area. The detector automatically records video of fire event (1 minute pre- and up to 3 minutes post-alarm initiation). These features, along with the built-in event logger, provide additional means to study the cause and development of fire events
Specification | Detail Description |
---|---|
DETECTION TIME AND DISTANCE | 4Oms for fast burst of explosion O.7s for 320 (O.8m) hydrogen fire at 0-100 ft. (O-3Om) |
FIELD OF VIEW | 90° Horizontal, 75° Vertical |
TIME DELAY | 0-30 seconds (Adjustable) |
BUILT-IN TEST | Automatic and Manual |
HD VIDEO | Allows clear imaging of fire and people at 100 ft. (3Om) distance |
VIDEO RECORDING OF ALARM EVENTS | 1-minute pre-event and 3 minutes post-event |
SYSTEM INTEGRATION | ONVIF (Open Network Video Interface Forum) |
OPERATING VOLTAGE | 24 VDC nominal (18-32 VDC) |
CURRENT CONSUMPTION | Standby |
Maximum | 25OmA all systems in operation (including window heater) |
ELECTRICAL ENTRIES | 2x conduit entries 3/4" 14NPT or M25x1.5 |
WIRING | 12-2OAWG (2.5-O.35mm2) |
RELAYS | Volt-free contacts rated 2A at 30 VDC Alarm - normally open Fault - normally closed |
INDICATION | Tri-color LED |
MODBUS | RTU compatible on RS-485 |
DIGITAL (FOR VIDEO) | IP network IEEE 802.3 10Base-t |
COMPOSITE VIDEO | NTSC or PAL |
MECHANICAL SPECS | 7.87 x 5.12 x 5.12" (200x130x130mm) |
TEMPERATURE RANGE | Operating |
HUMIDITY | Up to 99% (RH), non-condensing |
INGRESS PROGRESSION | IP66 & 67; NEMA 250 4X & 6P |
APPROVALS | (Explosion proof) ATEX |
Ex db eb IIC T5 Gb -55°C | |
IIIC T95°C Db -55°C | |
IIC T5 Gb -55°C | |
IIIC T105°C Db -55°C | |
Class I, Div. 1, Groups B, C & D; Class II, Div. 1, Groups E, F & G; Class III | |
PERFORMANCE (PENDING) | ANSI FM 3260 |
FUNCTIONAL SAFETY (PENDING) | SIL2, per IEC 61508 |
ACCESSORIES | Weather shield |
WARRANTY | 5 years |
Datasheet
F-Guard H2-HD datasheet 2021.pdf 1.07 MB
Manual - Current versions
F-Guard IR3-HD-H2 Manual 2022.pdf 2.28 MB
Approvals
EUTEC 0440.pdf 2.21 MB
FM20CA0021X.pdf 274.44 KB
FM20US0049X.pdf 238.6 KB
IECEx_FMG_20.0012_000.pdf 130.18 KB
Software
F-Guard Communicator Software.zip 16.08 MB
X100P0010.11.msi_.zip 16 MB
F-Guard H2-HD datasheet 2021.pdf 1.07 MB
Manual - Current versions
F-Guard IR3-HD-H2 Manual 2022.pdf 2.28 MB
Approvals
EUTEC 0440.pdf 2.21 MB
FM20CA0021X.pdf 274.44 KB
FM20US0049X.pdf 238.6 KB
IECEx_FMG_20.0012_000.pdf 130.18 KB
Software
F-Guard Communicator Software.zip 16.08 MB
X100P0010.11.msi_.zip 16 MB