Atmos Room Monitor
Atmos is a wall mounted device for controlled atmosphere. It should be installed where gas variation of concentration can put workers' safety at risk, or where gas concentration is to be monitored continuously for ambient storage conditions.
List of Benefits
- Dedicated to Room Monitoring where: O2 rate may decrease, CO or CO2 rate may increase
- Built-in audible alarm - External flash alarm optional
- From 1 to 3 channels
- Complies to EN 50 104 version 2010
Atmos is a wall mounted device for controlled atmosphere.
It should be installed where gas variation of concentration can put workers’ safety at risk, or where gas concentration is to be monitored continuously for ambient storage conditions.
The sensors can be remotely installed and sample the ambient atmosphere by natural diffusion or convection.
The central unit manages alarms with adjustable thresholds, and duplicates measurements to 4-20 mA outputs.
Three key features make this instrument invaluable :
SAFETY, ADAPTABILITY and CONTROL.
- Dedicated to Room Monitoring where:
- O2 rate may decrease
- CO or CO2 rate may increase
- Built-in audible alarm - External flash alarm optional
- From 1 to 3 channels
- Complies to EN 50 104 version 2010
KEY FEATURES
- User friendly
- Built-in audible alarm
- Qualified Gas : O2, CO2, CO, C2H4
- Up to 3 gas sensors for 1 central unit
- Extensions possible up to 24 digital connections
- Long distance between remote sensor & central unit
- Up to 1 km without signal amplifier
- IP65 central unit housing
- IP54 for remote sensors
- Atmospheric variation compensation
- Independent of weather and altitude variation
- 1 analog output 4-20 mA per sensor
- 2 alarm thresholds per gas channel
- 1 system fault relay
- Optional RS 485
POTENTIAL USERS
- Packaging Machine - MAP
- Biochemical department : Hospitals, laboratories, etc.
- Gas storage
- Cryogenic applications
- Fast food and industrial kitchens
- Freezing tunnels
- Fruit producers
- Cereal storage
- Car and trucks parks
- Carbonated drinks
- Cellars
- Beer, wine, etc.
- Gas Producers
- And many more …
Specification | Detail Description |
---|---|
OXYGEN(O2) | |
Accuracy | +/- 1% relative |
Resolution | 0.1% |
Scale | 0 - 25% ; other scales by request |
CARBON DIOXIDE (CO2) | |
Accuracy | +/- 2% full scale |
Resolution | 0.1% |
Scale | 0 - 5% ; other scales by request |
CARBON MONOXIDE (CO) | |
Accuracy | +/- 2% full scale |
Resolution | +/- 1ppm |
Scale | 0 - 2000 ppm ; other scales by request |
DEVICE | |
Central Enclosure | ABS enclosure IP 65 |
Dimensions | D90 or D150 W270 H250 (mm) |
Ports | 2 alarm relays per channel, + 1 fault relay 220 VAC 2A - 30 VDC-1A, Up to 3 analog outputs 4-20 mA |
Interface | 2 lines of 20 characters - soft keypad |
Power supply | 12V - 10W or 100-230 VAC – 50-60 Hz |
Temperature | 0 / 40°C - 98% RH |