Part Number: 72-8050-A50

A50 CO2 Detector

The essential safety tool for the hospitality and brewing industries. This plug and play CO2 detector is simple to wall mount in the area where CO2 is stored or piped and will provide audio/visual alarms should there be a leak which exceeds permissible levels.

List of Benefits

  • no calibration required (Pending local regulations)
  • Plug and play
  • Comply easily
  • Includes repeater for versatile safety

 

The Experts in Beverage and Hospitality Gas Safety.

This plug and play CO2 detector is simple to wall mount in the area where CO2 is stored or piped and will provide audio/visual alarms should there be a leak which exceeds permissible safety levels. The unit does not require any calibration unless local regulations mandate it.

If you are also using nitrogen you may also be interested in a dual A50 which contains both a CO2 and O2 sensor.

We also offer the A50M which consists of 2 x CO2 sensor units and one combined repeater - this is most commonly used in areas larger areas or in cellars which have a separate cold store.

The A50 is an affordable, easy to operate CO2 monitor and is ideal for ensuring safety in areas where the gas is piped or stored such as in a cellar or fast food restaurant.

The main sensor unit is to be wall-mounted in the area highlighted as a risk.  It is also supplied with a repeater which can be placed at the entrance to warn anyone entering the room of an alarm before entering.

Commonly Found in

  • Pub cellars
  • Fast food restaurants
  • Nuclear power plants
  • Breweries
  • Craft breweries
  • Wineries
  • Cider barns
  • Cafes
  • Night clubs
  • Kitchens
  • Sports stadiums
  • Swimming pools, spas, leisure centres
SpecificationDetail Description
Gas detected Carbon Dioxide (optional Oxygen sensor may be fitted)
Measurement technique Infra-Red (Oxygen - electrochemical)
Range 0.1 to 5% (Oxygen - 0.1 to 25%)
Resolution 0.01% (Oxygen - 0.1%)
Alarm set points 0.5 and 1.5% (optional alarm set points available) (Oxygen - 18 and 19.5%)
Response time 45 seconds to T90 (Oxygen - 15 seconds to T90)
Warm up time 40 seconds (Oxygen - 10 seconds)
CO2 Expected life > 15 years
O2 Expected life 1 year
Analyser specifications
Analyser type Fixed
Operating Temperature -5 to +40ºC
Power 230V AC, 110V AC, 9 to 24V DC (24 hour battery backup available)
Power consumption <5 VA
Output options 2 x relays, 0 to 1V
Dimensions 175 x 110 x 75mm (analyser) 72 x 170 x 45mm (repeater)
Sounder Minimum 75dbA
Internal Strobe Intensity >100cd
IP Rating IP65 (apart from quick connect repeater which is IP43)
Certifications and approvals CE, EN50270:1999, EN61000-6-3:2001+A11:2004, BS EN 61010-1:2001, IEC 61010-1(2ed), DIN 6653-2:2004 (TRSK313) and AS61010.1-2003 (Australia& New Zealand), CSA, Master Contract 239512, Certificate 1909026.
Warranty 2 years electrical
CO2 Sensor > 15 Years
O2 Senosr 2 years
 

Share this