Sensepoint XCD
The Sensepoint XCD range provides comprehensive monitoring of flammable, toxic and oxygen gas hazards in potentially explosive atmospheres, both indoors and outdoors.
List of Benefits
- Tri-Colour Backlit LCD
- Non-Intrusive Calibration
- 4-20mA and MODBUS Outputs
- Weatherproof Cap as Standard
Users can modify detector operation using the LCD and magnet switches without ever needing to open the unit. This enables one-man, non-intrusive operation and reduces routine maintenance time and costs.
A tri-color backlit LCD clearly indicates the unit’s status at a glance, even from a distance. A steady green backlight indicates normal operation, flashing yellow indicates fault and flashing red indicates an alarm. All detectors are supplied pre-configured and include 2 programmable alarm relays, 1 programmable fault relay as well as an industry standard 4-20mA output (sink or source selectable) and MODBUS. The scale, range, relay operation, alarm set point and electronic tag number of the detector can be adjusted using the transmitter’s LCD and non intrusive magnetic switches. Outputs are automatically inhibited during adjustment, thereby reducing the risk of false alarm at the control panel during maintenance.
Sensepoint XCD has an integral mounting plate for surface mounting or can be mounted to a horizontal or vertical pipe using the optional pipe mounting bracket. Electrical installation can be made using either conduit or cable with suitable mechanical protection. Two M20 or 3/4” NPT entries are provided (depending on certification). A weatherproof cap is also included for use in the harshest outdoor conditions. Other optional accessories include a sunshade/deluge protection, duct mounting kit, collecting cone and remote mounting sensor socket.
Sensepoint XCD ensures easy installation and the fastest routine operation by removing the need for hot work permits in hazardous areas. Using easy to replace plug-in sensors, downtime is also reduced and on-going costs are minimised through the use of poison resistant flammable sensors, poison immune infrared Hydrocarbon sensors and patented Surecell toxic sensors.
Specification | Detail Description |
---|---|
Input voltage range | 12 to 32 VDC (24 VDC nominal) |
Max power consumption | Maximum power consumption is dependant on the type of gas sensor being used. Electrochemical cells = 3.7W, IR=3.7W and Catalytic = 4.9W. Maximum inrush current = 800mA at 24VDC |
Current output relays | Sink or source. 3 x 5A@250VAC. Selectable normally open or normally closed (switch) and energized/de-energized (programmable). Alarm relays default normally open/de-energized. Fault relay default normally open/energized. |
Communication | RS485, MODBUS RTU |
Material | Housing |
Sensor | 316 stainless steel |
Weight (approx) | Aluminium alloy LM25 |
Mounting | Integral mounting plate with 4 x mounting holes suitable for M8 bolts. Optional pipe mounting kit for horizontal or vertical pipe 1.5” to 3” (2” nominal) |
Cable entries | UL/cUL versions |
IP Rating | IP66 in accordance with EN60529 |
Certified temperature range | -40℃ ~ +65℃ |
Certification | US, Latin America, Canada & Europe |
Performance | UL508; CSA 22.2 No. 52 (Flammable gases, excludes infrared sensors); ATEX, IEC/EN60079-29-1 |
SensepointXCD-Datasheet.pdf 158.23 KB
Manual - Current versions
Honeywell Sensepoint XCD Remote Flammable Detector Manual.pdf 5.19 MB
Sensepoint XCD Technical Manual.pdf 16.29 MB