SharpEye 20/20L-LB
UV/IR Flame Detector
i
This product has been discontinued and is no longer available. In many cases we can still service and calibrate it. Talk to our team about spares or alternatives.
The SharpEye 20/20L (and LB) is a combined UV/IR flame detector that pairs a solar-blind UV sensor with a narrow-band IR sensor for excellent sensitivity and enhanced immunity to false alarms. It offers a 20-millisecond response to a saturated signal and detects hydrocarbon, hydrogen, hydroxyl, metal and inorganic fires.
KEY BENEFITS
- Combined UV/IR dual-sensor detection
- Solar-blind design for high false-alarm immunity
- 20-millisecond response to a saturated signal
- Detects hydrocarbon, hydrogen, hydroxyl, metal and inorganic fires
- High-speed response
+ more in the Description tab below
Solar-Blind UV/IR Sensing With Millisecond Response
The SharpEye Model 20/20L (and LB) combined UV/IR flame detector employs a solar-blind UV sensor coupled with a narrow-band IR sensor, delivering excellent sensitivity together with enhanced immunity to false alarms.
The solar-blind design allows the detector to operate reliably even in the presence of sunlight, while the dual-sensor confirmation logic keeps nuisance alarms to a minimum. The detector achieves a 20-millisecond response to a saturated signal.
The 20/20L detects a broad range of fires, including hydrocarbon-based fuel and gas fires, hydrogen, hydroxyl fuels, and metal and inorganic fires. The LB version adds automatic and manual Built-In Test for self-checking.
Benefits
- Combined UV/IR dual-sensor detection
- Solar-blind design for high false-alarm immunity
- 20-millisecond response to a saturated signal
- Detects hydrocarbon, hydrogen, hydroxyl, metal and inorganic fires
- High-speed response
- User-programmable configuration
- Automatic and manual Built-In Test (BIT) on LB model
- Standard 4-wire connection with 4-20mA source output
- MTBF minimum 100,000 hours
- Backed by a 3-year warranty
Detection Principle
UV/IR (solar-blind UV plus narrow-band IR)
Fires Detected
Hydrocarbon fuel and gas fires, hydrogen, hydroxyl fuels, metal and inorganic fires
Response Time
20 msec to a saturated signal
False Alarm Immunity
Immune to false alarms (solar blind)
Configuration
User programmable
Built-In Test
Automatic and manual (BIT) on LB model
Wiring
Standard 4-wire connection
Output
4-20mA source (3-4 wires)
MTBF
Minimum 100,000 hours
Warranty
3 years
It uses a combined UV/IR design, pairing a solar-blind UV sensor with a narrow-band IR sensor for sensitivity and false-alarm immunity.
It provides a 20-millisecond response to a saturated signal.
It detects hydrocarbon-based fuel and gas fires, hydrogen, hydroxyl fuels, and metal and inorganic fires.
The solar-blind UV sensor lets the detector work reliably in daylight while maintaining enhanced immunity to false alarms.
The LB version adds automatic and manual Built-In Test (BIT) for self-checking of the detector.